The µCAN.4.ai-BOX is the extended universal measurement module for the acquisition of analogue standard signals.
The device is designed for measurement of ±10 V as well as 0(4)…20 mA signals with a
800 Hz total sampling rate.
| Parameter | Value |
|---|---|
| Channels | 4 analogue inputs |
| Signal types | ±10 V, 0–20 mA, 4–20 mA |
| Total sampling rate | 800 Hz |
| Protocol | CANopen (CiA 404; compliant with CiA 301, CiA 305, CiA 404) |
| Enclosure | Aluminium die-cast, IP66 |
| Status/Errors | 2 bi-color LEDs |
| Features | Anti-aliasing filter, heartbeat monitoring, automatic start-up |
| CAN bitrate | 50 kbit/s to 1 Mbit/s |
| CAN IDs | 11-bit (CAN 2.0A) and 29-bit (CAN 2.0B) |
| Termination | On-device switchable terminator |
Up to 4 analogue signals may be connected. Optional scaling of the measurement units is parameterised via CAN bus.
The digitised analogue values of the µCAN.4.ai-BOX are transmitted via CAN bus.
The CAN bus interface bitrate is adjustable from 50 kbit/s to 1 Mbit/s.
A terminating resistor can be enabled via a hardware switch.
The module’s CANopen implementation complies with CiA 301, CiA 305 and CiA 404.
Both 11-bit (CAN 2.0A) and 29-bit (CAN 2.0B) identifiers may be used for process data.
| Order Number | Description |
|---|---|
| 12.44.003 | µCAN.4.ai-BOX / Voltage / 16-bit — 4-channel analogue acquisition module with CANopen, signal type ±10 V DC, 16-bit resolution, designed for metric cable glands, connection via screw terminals. |
| 12.45.003 | µCAN.4.ai-BOX / Current / 16-bit — 4-channel analogue acquisition module with CANopen, signal type 0(4)…20 mA, 16-bit resolution, designed for metric cable glands, connection via screw terminals. |
| 12.46.003 | µCAN.4.ai-BOX / Voltage / 24-bit — 4-channel analogue acquisition module with CANopen, signal type ±10 V DC, 24-bit resolution, designed for metric cable glands, connection via screw terminals. |
| 12.47.001 | µCAN.4.ai-BOX / Current / 24-bit — 4-channel analogue acquisition module with CANopen, signal type 0(4)…20 mA, 24-bit resolution, designed for metric cable glands, connection via screw terminals. |
| 20.10.008 | µCAN.open.ER — Configuration tool for CANopen devices. |
| 90.01.114 | Metric cable installation kit for 4-channel modules. |
Copyright 2025 © All rights Reserved. Hemsida Webbdesign Interwebsite Webbyrå