µCAN.4.ti-BOX

  • 4-channel analogue input temperature
  • CAN protocol: CANopen CiA 404
  • Die-cast aluminium casing, protection class IP66
  • Indication of device status and errors by two bi-color LEDs
  • Sensor break and short circuit detection
  • Integrated cold junction compensation (thermocouples)
  • Connection of 2-/3-/4-wire sensors (resistance sensors)

µCAN.4.ti-BOX — 4-Channel Temperature Input Module

The µCAN.4.ti-BOX provides four inputs for measuring temperature sensors.
Signals from resistance sensors as well as thermocouples can be acquired at a total sampling rate of 400 Hz.
Sensor signals are evaluated and linearized within a rugged die-cast aluminium housing.
The CAN interface supports CANopen and SAE J1939 protocols.

Features

The µCAN.4.ti-BOX digitizes measurement values of temperature sensors and provides these values in °C
with a resolution of 0.1 °C. Module address and bitrate can be set via DIP switch or CAN bus (LSS, CiA 305);
automatic bitrate detection is also supported.

  • CAN protocol: CANopen CiA 404
  • Die-cast aluminium housing, protection class IP66
  • Device status and error indication via two bi-color LEDs
  • Sensor break and short-circuit detection
  • Integrated cold-junction compensation (thermocouples)
  • Connection of 2-/3-/4-wire sensors (resistance sensors)

Connectivity

Up to four measurement sensors can be connected to the module.
The sensor type is selected via CAN bus. When a thermocouple type is chosen,
cold-junction compensation activates automatically.

  • Platinum temperature sensors: Pt100, Pt500, Pt1000
  • Thermocouples: types J, K, L, T

Communications

The digitised temperature values of the µCAN.4.ti-BOX are transmitted via CAN bus.
The CAN bus bitrate is adjustable from 50 kbit/s to 1 Mbit/s.
A terminating resistor can be activated via a hardware switch.
The CANopen protocol complies with CiA 301, CiA 305 and CiA 404.
Both 11-bit (CAN 2.0A) and 29-bit (CAN 2.0B) identifiers may be used for process data.

Ordering Information
Order Number Description
12.43.005 µCAN.4.ti-BOX — 4-channel thermal data acquisition module with CANopen;
signal acquisition of J-, K-, N-, T-type thermocouples and Pt100, Pt500 and Pt1000 sensors;
16-bit resolution; designed for metric cable glands; connection via screw terminals.
12.43.705 µCAN.4.ti-BOX / Thermo type K — 4-channel thermal data acquisition module with CANopen;
signal acquisition via thermo plug-in connector type K; CAN and power supply via Sub-D 9-pole connectors.
20.10.008 µCAN.open.ER
— Configuration tool for CANopen devices.
90.01.114 Metric cable installation kit for 4-channel field modules.

Copyright 2025 © All rights Reserved. Hemsida Webbdesign Interwebsite Webbyrå

0
    0
    Your quote
    Your quote is emptyReturn